Cable Size CalculatorSizing and verification · free, no sign-up
Department of Electrical Power Systems Faculty of Power Engineering National University of Science and Technology POLITEHNICA Bucharest

Electrical cable size calculator

Size a new circuit or verify an existing cable using the technical criteria applied in electrical installation design. Results appear instantly in your browser, and every equation is explained in the Methodology section.

  • Voltage drop in normal operation
  • Voltage drop at motor start
  • Continuous current rating (Iz ≥ In)
  • Short-circuit thermal withstand

Load
kW
%
Network and cable
m
Installation conditions
°C
On the same tray or in the same trench, including this one
Motor starting
Short circuit

Methodology and equations

The calculation follows the basic electrotechnical principles of IEC 60364-5-52 and the Romanian standard I7-2011. The cross-section is derived analytically from the voltage-drop equation, rounded up to the next standard size, then checked for continuous current rating and, optionally, short-circuit withstand.

1. Load current

I = P / (√3 · U · cos φ)   (three-phase)
I = P / (U · cos φ)   (single-phase)

2. Voltage drop

ΔU = K · I · L · (r₀ · cos φ + x₀ · sin φ)

K = √3 for three-phase systems and K = 2 for single-phase systems. L is the length in km, r₀ = 1000 / (γ · S) [Ω/km], with γCu = 56 and γAl = 34 m/(Ω·mm²). The specific reactance x₀ is 0.08 Ω/km for multicore cables and single-core cables in trefoil, 0.095 Ω/km for single-core cables laid flat and touching, and 0.13 Ω/km for single-core cables laid flat with 1×D spacing.

3. Cross-section from the voltage-drop limit

S = 1000 · cos φ / ( γ · [ ΔUmax / (K · I · L) − x₀ · sin φ ] )

If the reactive term alone exceeds the allowed drop, no cross-section can meet the limit. In that case the tool switches to parallel conductors.

4. Continuous current rating

Iz = Iz0 · k₁ · k₂ ≥ In
k₁ = √( (θmax − θa) / (θmax − θref) )

θmax is 70 °C for PVC and 90 °C for XLPE/EPR; θref is 30 °C in air and 20 °C in ground. For XLPE/EPR insulation the Iz0 values are multiplied by 1.18. k₂ is the grouping factor: 1.00 for 1 circuit, 0.80 for 2, 0.70 for 3, 0.65 for 4, 0.60 for 5 and 0.57 for 6 or more circuits.

5. Short-circuit thermal withstand

Smin = Isc · √t / k
Factor kPVCXLPE / EPR
Copper115143
Aluminium7694

6. Sizing algorithm

  1. The required cross-section is computed for each active criterion: normal voltage drop, starting voltage drop and short circuit.
  2. The next standard size above the largest value is selected.
  3. If Iz < In, the size is increased until the current rating is met.
  4. The maximum size is 240 mm², or 630 mm² when explicitly allowed. Above it, the calculation is repeated automatically with one more conductor per phase (2, then 3) until a solution is found.

In verification mode the limits are ΔU ≤ 5 % in normal operation and ΔU ≤ 10 % at motor start.

Base current ratings Iz0 [A] (PVC insulation, in air, 30 °C)

S [mm²]1.52.54610162535507095120150185240300400500630
Copper19.52736466385112138168213258299344392461530634730830
Aluminium–212836496683103125160195226261298352406485560640
Note. This tool is intended for teaching and preliminary estimates. Its results do not replace design by a qualified engineer using the cable manufacturer's data and the applicable standards.

Frequently asked questions

How do you choose the cross-section of an electrical cable?

The cross-section must meet several conditions at once: the voltage drop must stay below the allowed limit, the cable's current rating (corrected for ambient temperature and grouping with other circuits) must be at least equal to the load current, and, where required, the cable must withstand the heating caused by the short-circuit current until the fault is cleared. The largest of the resulting sizes is kept and rounded up to the next standard cross-section.

How is voltage drop calculated on a three-phase cable?

Use ΔU = √3 · I · L · (r₀ · cos φ + x₀ · sin φ), with L in km and r₀, x₀ in Ω/km. For example, a 15 kW load at 400 V with a power factor of 0.85 draws 25.5 A. On a 100 m copper cable of 4 mm², the voltage drop is about 16.9 V, or 4.23 %.

What cable size do I need for 15 kW at 400 V?

It depends on the length, the conductor material and the installation method. For a 15 kW three-phase load at 400 V with a power factor of 0.85, supplied through an XLPE-insulated copper cable installed in air at 30 °C over 100 m, the result is 4 mm². The limiting criterion is the 5 % voltage drop, not heating. For other lengths or conditions, enter your data in the calculator.

Why check motor starting separately?

At start-up an induction motor draws several times its rated current (often 5 to 7 times) at a low power factor. The resulting voltage drop can prevent the motor from starting or disturb other loads, so the calculator checks it separately, with a default limit of 10 %.

What is the k factor in the short-circuit check?

The k factor depends on the conductor material and insulation and appears in Smin = Isc · √t / k. The values used are 115 for copper with PVC, 143 for copper with XLPE, 76 for aluminium with PVC and 94 for aluminium with XLPE. For example, a 6 kA fault lasting 0.1 s requires at least 13.27 mm² of XLPE-insulated copper.